Check how much voltage a DC cable run loses at a given load. Enter the current, the one-way length from the source to the load, the wire gauge and the system voltage. The calculator doubles the length for the return conductor and reports the drop in volts and as a percentage.
Whenever you add or move a DC load: a new windlass, a bow thruster, a fridge, a bilge pump moved aft. Too much drop makes motors slow and hot, starves electronics into resetting, and in the worst case leaves a pump unable to keep up. Too thick a cable costs money and weight. This finds the line between them.
Length is measured along the route the cable will actually take, from the battery or panel to the load. The return is assumed to run the same length back, so the calculator uses twice the number you enter.
R = Ω per 1000 ft × (2 × one-way length) ÷ 1000
drop (V) = current × R
drop (%) = drop ÷ system voltage × 100
The resistance values are for copper at room temperature. Hot engine rooms raise resistance a few percent.
Widely used marine practice sets two limits. Circuits where low voltage could affect safety (panel feeds, navigation lights, bilge pumps, electronics) are sized for no more than 3% drop. Other loads, such as cabin lights, may be sized for 10%. Windlasses and thrusters are usually sized to their maker’s cable table, which is often tighter than 10% because they draw so much current.
Windlass, 100 A, 10 ft run, 4 AWG, 12 V. R = 0.2485 × 20 ÷ 1000 = 0.00497 Ω; drop = 100 × 0.00497 = 0.50 V (4.1%). Over 3%, which a windlass can usually live with, but 2 AWG brings it to 2.6%.
Bilge pump, 5 A, 25 ft run, 14 AWG. R = 2.525 × 50 ÷ 1000 = 0.126 Ω; drop = 0.63 V (5.3%). Too much for a safety load; 12 AWG gives 3.3% and 10 AWG 2.1%.
Same windlass on 24 V. Half the current for the same power: 50 A on 4 AWG drops 0.25 V, which is 1.0% of 24 V.
| Gauge | 10 ft one-way | 15 ft | 20 ft | 30 ft |
|---|---|---|---|---|
| 14 AWG | 8.4% | 12.6% | 16.8% | 25.3% |
| 12 AWG | 5.3% | 7.9% | 10.6% | 15.9% |
| 10 AWG | 3.3% | 5.0% | 6.7% | 10.0% |
| 8 AWG | 2.1% | 3.1% | 4.2% | 6.3% |
| 6 AWG | 1.3% | 2.0% | 2.6% | 4.0% |
| 4 AWG | 0.8% | 1.2% | 1.7% | 2.5% |
Current goes out on the positive and back on the negative; both conductors add resistance.
Choose “Custom” and enter its resistance in ohms per 1000 ft, or convert: 1 Ω/km = 0.3048 Ω/1000 ft.
It means the drop is above the 3% or 10% guideline. Decide based on what the load is.